Supply voltage: 24V DC, permissible voltage range - 15% to + 20%.
Power Consumption: The current drawn from a 24V DC supply is approximately 5mA, with an inrush current of 0.05A²s at start-up and a maximum ripple of 5%.
Reverse Voltage Protection: Yes.
Maximum power consumption in the module: 1.1W.
Mounting position: horizontal or vertical, operating temperature range from 0°C to +60°C when installed horizontally, reduced output load to 50% per bank when installed vertically, and operating temperature range from 0°C to +40°C.
Cooling method: natural convection cooling, which cannot be obstructed by cable ducts or other components in the control cabinet.
Number and type of input channels: 2 configurable RTD channels.
Channel grouping: 1 group of 2 channels each.
Resolution: RTD of 0.1°C/0.1°F, resistance of 15 bits + sign bits.
Input Type: Modular Ground Reference RTD for 2-Wire and 3-Wire RTD Temperature Detectors.
Input range: support PT100, PT1000, NI100, NI1000, 150Ω, 300Ω, etc.
Module update time: less than 1s for all channels.
Channel input resistance: >100kΩ.
Input filter attenuation: -3dB at 3.6kHz.
Analog Value Conversion Error: Typical values depend on the RTD and are up to ±0.6% of full scale at 25°C and up to ±2% of full scale at 0°C to 60°C or electromagnetic interference.
A/D conversion time: 140ms typical per channel.
Unused Input: Openable and should be configured as Unused.
Input data length: 4 bytes.
Sensor internal power consumption: 1mW max.
Interference suppression: can be carried out upon request.
Maximum input voltage: 30V DC at the detection end and 5V DC at the source side.
Basic error (resistance): 0.1% of full scale.
Repeatability: 0.05% of full scale.
Overvoltage Protection: Yes, up to 30V DC.
Wire loop resistance: <20Ω. Maximum cable length: 10m for unshielded wires and 100m for shielded wires. Galvanic isolation: The input group is galvanically isolated from the rest of the module to prevent interference from the internal power supply and other modules. Degree of protection: IP20 housing. Operating humidity: 95% max, non-condensing. Working air pressure: >800hPa/<2000m.
4.9
12 views
Reviews
Reviews
Q How to make a payment?
E****R 18/11/2024
A We accept various payment methods including bank transfers, credit cards, and PayPal. Please refer to our payment page during checkout for detailed instructions on how to complete your payment. If you have any questions or need assistance with payment, please contact our customer support team.
18/11/2024
Q How will the products be shipped?
T****k 16/08/2024
A We ship products through reliable courier services such as DHL, UPS, and FedEx. Shipping fees and delivery times may vary depending on the destination. You will receive a tracking number once your order has been dispatched, allowing you to track the status of your shipment. Please note that shipping times may vary based on location and availability.
16/08/2024
Q How is warranty provided?
L****Y 08/05/2024
A We offer a warranty on all of our products. The warranty period and conditions vary depending on the product category. For specific warranty information, please refer to the product page or your purchase agreement. If you encounter any issues with a product during the warranty period, please contact our customer service team with your proof of purchase, and we will guide you through the warranty claim process.
08/05/2024
★ ★ ★ ★ ★ 16/08/2024
Good service!
(156)
★ ★ ★ ★ ★ 23/07/2024
Good!
(982)
★ ★ ★ ★ ★ 23/07/2024
Good quality!
(982)